background
TR  EN  DE  RU

Products

Back to products list
Birtaş Kablo
Silicone Cables
SIA & H05S-U
SIAF & H05S-K
SIAF-GL & H05SJ-K
SIMH / SIHF
H05SS-F
SIHF EWKF
H05SS-F EWKF
SIMH-FR FE 180
SIMH-FR/PF FE 180
SIMH-SPEC
H05SC4S-K…(SIMH C1)
H05SSC4S-K…(SIMH C2)
SIMH-GL
SIMH-GLS (GLP)
H05SSQS-K…(SIMH-S)
LISHCSH FE 180–E30/E90
JE-SH(St)SH FE 180-E30/E90 …Bd Z
BUJI CABLE – 7 / 10 kV
BUJI CABLE – 16 / 20 kV
N2GFAF
N2GMH2G
LISH(St)CSH-TIMF SPEC
Product Download Files
Birtaş Kablo - Kumanda Kabloları 2YSLCY-J
Product Data Sheet
Local Quality Certificates
International Quality Certificates
Product Price List
Test Reports
Package Style
Summary Table
Reference Samples
EREGLI STEEL
ISKENDERUN STEEL
KARABÜK STEEL
MITTAL STEEL-ROMANYA
COLAKOGLU METALURJİ
KASTAMONU ENTEGRE
SILICONE CABLES
JE-SH(St)SH FE 180-E30/E90 Bd Z
HIGH TEMPERATURE, SCREENED DATA SILICONE CABLES
Marking

BIRTAS KABLO JE-SH(St)SH FE 180 E 30/E 90 Bd Z 4 x 2 x 0.80mm 1720 04 004 Part no GOST-R CE....mt

Applications

These cables fields of use as a control and power supply cable they are fire proof and halogen free cables which, on the basis of a fixed operating mode, can continue with the supply of a power for a period of 180 minutes under the existing fire conditions (at a temperature of 750OC and under the flames). Also these cables shall satify EN50200 test which is a fire resistant with mechancal shock test, Also these cables are used for industrial electronics, telecommunication , control, data engineering where low current consumptions are required and transmision of the data must be continuous where the information and transmission systems,the transmission of analogue and digital signals in processor-controlled equipment. The screen protects against external pulses and ensures an interference-free transmission.These cables are used at schools, airpots, hospitals, etc. and in the environments which have no corrosive gases are emitted in the event of fire.

Cable Design
ConductorPlain copper conductor, solid
InsulationSpeacial silicone rubber compound
Core identificationVDE 0815 (Z)
PairTwo conductors twisted to a pair
Bundle4 pairs laid up to a bundle
Bundle identificationBy spirals with imprinted numbers
Lay-upCores laid up in layers of optimum pitch
Cores laid up in layers of optimum pitch
SeparatorPolyester tape
ScreenTinned Cu drain wire under the AL-PES tape
Outer sheathSpeacial silicone rubber compound
Sheath colourRAL 2009, Orange or RAL 3000, Red
Technical Data
StandardVDE 0250, DIN VDE 0815
(Designed according to)
Insulation resistanceMin. 100 MΩ.km
Mutual Capacitance (800 Hz)Max. 120 nF/km
* This value may be exceeded by 20% by cables with up to 4 pairs.
Capacity UnbalancedMax. 200 pF / 100 mt
* 20% of the values, at least one value up to 400 pF permitted
Operating voltage, peakMax. 225 V
Test voltagecore/core: 500 V
core/screen: 2000 V
Temperature rangeSabit: - 60 oC ~ + 180 oC
Esnek: - 25 oC ~ + 180 oC
Min. bending radiusFixed: 4 x D
Mobile: 15 x D
Flame retardance testIEC 60332-1 & EN 50265-2-1
IEC 60332-3 & EN 50266-2-4
Insulation integrityIEC 60331 , VDE 0472-814
Fire resistant with mechanical shock
*Upon request
DIN EN 50200 ; PH 15 (15 minutes)
DIN EN 50200 ; PH 30 (30 minutes)
DIN EN 50200 ; PH 60 (60 minutes)
DIN EN 50200 ; PH 90 (90 minutes)
Cross Section
Part-NumberNo. of Cores x
Cross Section (mm2)
Approx. Outer Diameter (mm)Copper Weight (Kg/km)Approx. Cable Weight (Kg/km)
1120 04 0022x2x0,807,22185
1120 04 0044x2x0,8010,541135
1120 04 0088x2x0,8016,582320
1120 04 01212x2x0,8018,5123340
1120 04 01616x2x0,8020,0164445
1120 04 02020x2x0,8021,8205550
1120 04 02424x2x0,8025,9245690
1120 04 02432x2x0,8028,4322875
1120 04 02440x2x0,8033,64051125
1120 04 05252x2x0,8036,75251315
Top 
Copyright © Etabir Birlesik Kablo Sanayi ve Ticaret A.S. - 2012. All rights reserved. design: plusmax